IEC60502, GB/T12706 or other standard required by customer.
The requirements for flame retardant property is according to IEC60332-3 and GB18380.
Packing:Steel/wooden reel,wooden reel or steel reel.
XHIO1RV Cable voltage:3.6/6KV(7.2KV) 8.7/15KV(17.5KV) 12/20KV (24KV) 18/30KV(36KV)
Installation Temperature : The installation temperature should be over 0℃ . If the ambient temperature is lower than 0℃,the cable should be preheated.
Operating Temperature : Max permissible continuous operating temperature of conductor shall not exceed 90℃ .
Conductor Short-circuit Temperature : Max temperature at short-circuit shall not exceed 250℃ . The short-circuit duration shall not exceed 5 seconds.
This product is suitable for transmission and distribution system at the voltage from LV to MV. The power cables can be flame retardant when used as type ZR.
Description |
Cu or Al conductor/ XLPE insulated/ steel tape armored/ PVC sheathed flame retardant power cable CU/XLPE/CTS/STA/PVC |
Cu or Al conductor/ XLPE insulated/ steel tape armored/ PVC sheathed power cable CU/XLPE/CTS/STA/PVC |
Cu or Al conductor/ XLPE insulated/ steel wire armored/ PVC sheathed power cable CU/XLPE/CTS/SWA/PVC |
Cu or Al conductor/ XLPE insulated/ steel wire armored/ PVC sheathed flame retardant power cable CU/XLPE/CTS/SWA/PVC |
Technical Characteristics
3-Core XHIO1RV cable 18/30KV
Nominalconductor crosssectionarea (mm) | Nominal Insulation thickness (mm) | Max DC Conductor resistance at20℃ (Ω/km) | |
Cu | KG | ||
3x50 | 8.0 | 1.83 | 820 |
3x70 | 8.0 | 1.15 | 1450 |
3x95 | 8.0 | 0.727 | 1850 |
3x120 | 8.0 | 0.524 | 2300 |
3x150 | 8.0 | 0.387 | 2650 |
3x185 | 8.0 | 0.268 | 3650 |
3x240 | 8.0 | 0.193 | 4550 |
3x300 | 8.0 | 0.153 | 5450 |
3x400 | 8.0 | 0.124 | 7000 |