LV PVC power cable

0.6/1kV PVC Insulated Power Cable

  • Bending Radius:20( d+D) +/-5% for single core cable,15( d+D )+/-5% for multi-core cable.
    D=Actual outer diameter of cable (mm),d=Actual diameter of the conductor (mm)

Description

Installation Temperature: The installation temperature should be over 0℃,If the ambient temperature is lower than 0℃,the cable should be preheated.

Operating temperature: Max permissible continuous operating temperature of
conductor shall not exceed 70℃ .

Conductor Short-circuit Temperature: Max temperature at short-circuit shall conductor shall not exceed 160℃,The short-circuit duration shall not exceed 5 seconds.

Standard

IEC 12706,IEC60502 or other standard required by customer.
The requirements for flame retardant property is according to IEC60332-3 and GB18380.
Packing:Steel/wooden reel,wooden reel or steel reel.

Application

PVC insulated power cable is suitable for power supply and distribution circuits in manufacturing and processing plant,commercial building or residence at the rated voltage 0.6/1kV or less. The power cables can be flame retardant application when use fire retardant material related.

Parameters

DescriptionApplication
Cu  or  Al   conductor/PVC  insulated/PVC  sheathed/ power cableIt is installed in indoor,in duct or in tunnel,but unable to bear pulling force and pressure
Cu    or    Al    conductor/PVC    insulated/steel    tape armored/PVC sheathed/ power cableIt  is  installed  in  indoor,i  in  tunnel,directly   in ground,able to bear proper pressure
Cu    or    Al    conductor/PVC    insulated/steel    wire armored/PVC sheathed/ power cableIt is installed in indoor,in well,under water, able to bear proper pulling force
Cu  or  Al   conductor/PVC  insulated/PVC  sheathed/ flame retardant power cableIt is installed in indoor,in duct or in tunnel,but unable to bear pulling force and pressure
Cu    or    Al    conductor/PVC    insulated/steel    tape armored/PVC sheathed/ flame retardant power cableIt  is  installed  in  indoor,i  in  tunnel,directly   in ground,able to bear proper pressure
Cu    or    Al    conductor/PVC    insulated/steel    wire armored/PVC sheathed/flame retardant power cableIt is installed in indoor,in well,under water, able to bear proper pulling force

Supply Range

DescriptionNo of coresNominal conductor cross section area (mm2)
 Cu or Al conductor/PVC or flame retardant PVC insulated/PVC or  flame retardant PVC sheathed11.5 to 6301.5 to 630
21.5 to 4001.5 to 400
31.5 to 4001.5 to 400
42.5 to 4002.5 to 400
52.5 to 4002.5 to 400
Cu or Al conductor/PVC or flameretardant PVC insulated/steeltape or wire armor/PVC or flameretardant PVC sheathed  2,3,4,5  4 to 400  4 to 400

Technical Characteristics for CU or AL/PVC/PVC,SINGLE CORE

Nominalconductorcrosssectionarea(mm)Nominal  Insulation thickness  (mm)Nominalsheaththickness  (mm)ApproxOverallDiameter  (mm)Max DCConductorresistance   at20℃    (Ω/km) Approx weight of cable(kg/km)
CuAlCuAl
1x1.50.81.546.112.1---50.741.3
1x2.50.81.546.57.4112.163.547.9
1x41.01.547.44.617.4187.763.0
1x61.01.547.93.084.61111.075.9
1x101.01.549.21.833.02166.693.0
1x161.01.5410.31.151.91233.3132.2
1x251.21.5412.00.7271.20344.9185.4
1x351.21.5413.20.5240.868449.8228.7
1x501.41.5414.90.3870.641590.5289.8
1x701.41.5416.70.2680.443807.3374.2
1x951.61.6519.30.1930.3201102.0501.4
1x1201.61.6520.90.1530.2531349.0590.3
1x1501.81.7623.10.1240.2061654.0721.3
1x1852.01.8725.60.09910.1642060.0891.6
1x2402.21.9828.80.07540.1252651.01114.0
1x3002.42.0931.90.06010.1003323.01396.0
1x4002.62.2035.50.04700.07784205.01742.0
1x5002.82.3139.70.03660.06055359.02128.0
1x6302.82.4043.70.02830.04696707.02605.0

Technical Characteristics for CU or AL/PVC/PVC,2 CORES

Nominalconductorcrosssectionarea(mm)Nominal  Insulationthickness (mm)Nominalsheaththickness(mm)ApproxOverallDiameter(mm)Max DC Conductorresistance   at20℃    (Ω/km)Approx weight ofcable(kg/km)
CuAlCuAl
2X1.50.81.810.512.1---119.0100.0
2X2.50.81.811.37.4112.1150.0118.0
2X41.01.813.14.617.41210.0160.0
2X61.01.814.13.084.61264.0192.0
2X101.01.816.71.833.02393.0242.0
2X161.01.818.81.151.91541.0334.0
2X251.21.819.60.7271.20794.0469.0
2X351.21.821.80.5240.8681037.0585.0
2X501.41.825.10.3870.6411227.0620.0
2X701.41.928.20.2680.4431650.0747.0
2X951.62.029.20.1930.3202213.0988.0
2X1201.62.131.30.1530.2532733.01186.0
2X1501.82.234.70.1240.2063396.01462.0
2X1852.02.437.90.09910.1643943.01559.0

Technical Characteristics for CU or AL/PVC/PVC,3-CORES

Nominalconductorcrosssectionarea(mm)Nominal  Insulation thickness  (mm)Nominalsheaththickness  (mm)ApproxOverallDiameter  (mm)Max DCConductorresistance   at20℃    (Ω/km) Approx weight of cable(kg/km)
CuAlCuAl
3X1.50.81.810.912.1---142113
3X2.50.81.811.87.4112.1187139
3X41.01.813.74.617.41265189
3X61.01.814.83.084.61335227
3X101.01.817.61.833.02514290
3X161.01.819.91.151.91728419
3X251.21.823.60.7271.201084596
3X351.21.826.10.5240.8681422745
3X501.41.826.50.3870.6411801834
3X701.41.928.80.2680.44324151061
3X951.62.133.60.1930.32032051418
3X1201.62.237.10.1530.25340371716
3X1501.82.341.90.1240.20650282127
3X1852.02.545.90.09910.16461802602
3X2402.22.751.80.07540.12579493308
3X3002.42.855.30.06010.10097803979

Technical Characteristics for CU or AL  PVC  PVC,4-CORES

Nominalconductorcrosssectionarea(mm)Nominal  Insulation thickness  (mm)Nominalsheaththickness  (mm)ApproxOverallDiameter  (mm)Max DCConductorresistance   at20℃    (Ω/km) Approx weight of cable(kg/km)
CuAl Al
4X2.50.81.812.77.4112.1232169
4X41.01.814.94.617.41322221
4X61.01.816.13.084.61422271
4X101.01.819.21.833.02649388
4X161.01.821.71.151.91922509
4X251.21.825.90.7271.201373722
4X351.21.828.70.5240.8681802899
4X501.41.930.40.3870.64123801091
4X701.42.033.90.2680.44332021398
4X951.62.239.70.1930.32043151866
4X1201.62.344.20.1530.25353592265
4X1501.82.548.70.1240.20666792811
4X1852.02.653.50.09910.16481903420
4X2402.22.955.40.07540.125104944305
4X3002.43.160.20.06010.100129485215

Technical Characteristics for CU or AL/PVC Insulated/Steel Tape Armored/PVC

sheathed Power Cable, 2-CORES

Nominalconductor crosssectionarea(mm)Nominal  Insulation thickness  (mm)NominalBeddingThickness  (mm)Nominalsheaththickness  (mm)ApproxOverallDiameter  (mm)Max DCConductorresistance   at20℃(Ω/km)Approxweight ofcable(kg/km)
CuAlCuAl
2X41.01.21.813.14.617.41210160
2X61.01.21.814.13.084.61264192
2X101.01.21.816.71.833.02393242
2X161.01.21.818.81.151.91541334
2X251.21.21.822.20.7271.20794469
2X351.21.21.824.50.5240.8681037585
2X501.41.21.821.80.3870.6411227610
2X701.41.21.924.70.2680.4431650747
2X951.61.22.029.20.1930.3202213988
2X1201.61.22.131.30.1530.25327331186
2X1501.81.32.234.70.1240.20633961462
2X1852.01.42.239.20.09910.16441121726

Technical Characteristics for CU or AL/PVC Insulated/Steel Tape Armored /PVC

sheathed Power Cable, 3-CORES

Nominalconductor crosssectionarea(mm)Nominal  Insulation thickness  (mm)NominalBeddingThickness  (mm)Nominalsheaththickness  (mm)ApproxOverallDiameter  (mm)Max DCConductorresistance   at20℃(Ω/km)Approxweight ofcable(kg/km)
CuAlCuAl
3X41.01.21.817.34.617.41489414
3X61.01.21.818.43.084.61577472
3X101.01.21.821.21.833.02800559
3X161.01.21.823.51.151.911050740
3X251.21.21.827.20.7271.201465976
3X351.21.21.930.70.5240.86821491372
3X501.41.22.031.30.3870.64124531486
3X701.41.22.133.60.2680.44331161763
3X951.61.22.238.30.1930.32040532216
3X1201.61.32.341.90.1530.25349302609
3X1501.81.42.547.10.1240.20660753174
3X1852.01.42.650.90.09910.16472993721
3X2402.21.52.857.00.07540.12592134590
3X3002.41.73.061.10.06010.100111855438

Technical Characteristics for CU or AL/PVC Insulated/Steel Tape Armored/PVC

sheathed Power Cable, 4-CORES

Nominalconductor crosssectionarea(mm)Nominal  Insulation thickness  (mm)NominalBeddingThickness  (mm)Nominalsheaththickness  (mm)ApproxOverallDiameter  (mm)Max DCConductorresistance   at20℃(Ω/km)Approxweight ofcable(kg/km)
CuAlCuAl
4X41.01.21.818.54.617.41565464
4X61.01.21.819.73.084.61685533
4X101.01.21.822.81.833.02960699
4X161.01.21.825.31.151.911273851
4X251.21.21.930.50.7271.2019981347
4X351.21.22.033.50.5240.86825051602
4X501.41.22.135.20.3870.64131221832
4X701.41.22.238.70.2680.44340252220
4X951.61.32.344.70.1930.32052912842
4X1201.61.42.549.40.1530.25364643370
4X1501.81.42.653.70.1240.20678663998
4X1852.01.52.858.90.09910.16495424772
4X2402.21.73.061.00.07540.125119165727
4X3002.41.83.366.20.06010.100145016767

Technical Characteristics for CU or AL/PVC Insulated/Steel Wire Armored/PVC CU/PVC/SWA/PVC Sheathed Power Cable, 2-CORES

Nominalconductor crosssectionarea(mm)Nominal  Insulation thickness  (mm)NominalBeddingThickness  (mm)Nominalsheaththickness  (mm)ApproxOverallDiameter  (mm)Max DCConductorresistance   at20℃(Ω/km)Approxweight ofcable(kg/km)
CuAlCuAl
2X41.01.21.818.74.617.41723672
2X61.01.21.819.93.084.61818744
2X101.01.21.822.31.833.021044802
2X161.01.21.825.21.151.9114321225
2X251.21.21.928.80.7271.2018481522
2X351.21.21.931.10.5240.86822002003
2X501.41.22.028.60.3870.64122651620
2X701.41.22.131.50.2680.44328101907
2X951.61.22.336.20.1930.32035822357
2X1201.61.22.438.30.1530.25341902643
2X1501.81.32.542.90.1240.20653923459
2X1852.01.42.748.00.09910.16465905340

Technical Characteristics for CU or AL/PVC Insulated/Steel Wire Armored/PVC

Sheathed Power Cable, 3-CORES

Nominalconductor crosssectionarea(mm)Nominal  Insulation thickness  (mm)NominalBeddingThickness  (mm)Nominalsheaththickness  (mm)ApproxOverallDiameter  (mm)Max DCConductorresistance   at20℃(Ω/km)Approxweight ofcable(kg/km)
CuAlCuAl
3X41.01.21.819.34.617.41798722
3X61.01.21.820.63.084.61908799
3X101.01.21.822.11.833.021183965
3X161.01.21.926.31.151.9116581349
3X251.21.21.930.20.7271.2021901701
3X351.21.22.032.70.5240.86826351957
3X501.41.22.133.30.3870.64130502083
3X701.41.22.235.60.2680.44337552401
3X951.61.22.341.50.1930.32051623324
3X1201.61.32.445.10.1530.25361433822
3X1501.81.42.651.60.1240.20680255124
3X1852.01.42.855.60.09910.16494285850
3X2402.21.53.061.70.07540.125116126971
3X3002.41.73.265.80.06010.100137817980

Technical Characteristics for CU or AL/PVC Insulated/Steel Wire Armored/PVC

Sheathed Power Cable,4-CORES

Nominalconductor crosssectionarea(mm)Nominal  Insulation thickness  (mm)NominalBeddingThickness  (mm)Nominalsheaththickness  (mm)ApproxOverallDiameter  (mm)Max DCConductorresistance   at20℃(Ω/km)Approxweight ofcable(kg/km)
CuAlCuAl
4X41.01.21.820.14.617.41874773
4X61.01.21.821.73.084.611130978
4x101.01.21.825.61.833.0215151254
4x161.01.21.828.11.151.9119241502
4x251.21.22.032.70.7271.2025701919
4x351.21.22.135.70.5240.86831302227
4x501.41.22.137.20.3870.64137952505
4x701.41.22.341.90.2680.44351473342
4x951.61.32.547.90.1930.32065864137
4x1201.61.42.653.90.1530.25385145420
4x1501.81.42.858.40.1240.206101166248
4x1852.01.53.063.60.09910.164120077237
4x2402.21.73.265.70.07540.125144608271
4x3002.41.83.470.70.06010.100172499515

Leave A Message